5-183
Linear motor keypad alignment
1. Set the Cn085 magnetic pole detection voltage level.
2. Set automatic detection of the dn-11.0 magnetic pole position to 1; Auto will be displayed
on the keypad panel.
3. After aligned successfully, the panel will again display dn-11; if alignment fails, it will
display AL.032 linear motor magnetic pole alignment abnormal.
Cn085 Magnetic pole angle position automatically detects the alignment duty
Initial Value Unit Setting Range Effective RS-485 Address
15 % 0 ~ 100
Take effect after
settin
g
0058H
Setting description: Use motor pole alignment and adjust the amount of current during alignment. The
adjustment range is a percentage of the VDC voltage
If there were no problems with all the actions above, Cn009.2=0~6 can be set according to
customer needs to determine future magnetic pole alignment timings.Customers can choose to connect
to the DI pin (Open Collector) or the fully-closed circuit pin (line driver) according to the feedback
electrical features of the Hall signal itself.If set as Hall feedback alignment, there is no need to use
dn-11.0 magnetic pole angle automatic detection.
Cn009.2 Alignment setting when power is connected to the linear motor for the
first time
Initial Value Unit Setting Range Effective RS-485 Address
0 -- 0 ~ 4
Takes effect after
confirmation
000AH
Setting description:
Setting Description
0 Set dn-11 manually to complete alignment.
1 Automatic alignment after excitation
2 Automatic alignment after power on
3
Use the DI pin to input Hall signal, and use Hall signal
alignment and reset to zero
4
Use the DI pin to input Hall signal, and use Hall signal
alignment
5
Use fully-closed circuit pin to input Hall signal, and use Hall
signal alignment and reset to zero
6
Use fully-closed circuit pin to input Hall signal, and use Hall
si
g
nal ali
g
nment
Note: The U phase Hall signal must be aligned with the zero point of the U phase opposite
potential
G2S range: 0~6
G2E/G2SE/E2 range: 0~4