6-14
5. When tuning fails and generates an alarm, adjustment can be performed according to the handling
guidelines. When completed tuning, you can select whether or not to Write Parameter. Lastly, click on
"Exit" to complete automatic gain adjustment.
Automatic Gain Adjustment Alarm and Handling Actions
When an error occurs in the automatic gain adjustment process, adjustments can be made through the
following counter-measures:
AL.003 Motor Overload
Cause Counter-measure
The system generates large
amplitude vibrations
Increase the load inertia ratio (Cn025) until the system can
operate steadily
AL.035 Tuning Failed
Cause Counter-measure
The System generates
Vibration Resonance or
Acoustic Resonance
Decrease the System Rigidity (Cn026) until the System can operate
steadily
Execute PC-Link Mechanical Characteristics Analysis Function
Observation to observe if resonance exists with the system and suppress it
Automatic gain adjustment related parameters
Cn025 Load inertia ratio
Initial Value Unit Setting Range Effective RS-485 Address
10 0.1 0 ~ 2000
Effective after
confirmation
001CH
Setting description:
Loadinertiaratio
Loadinertia󰇛JL󰇜convertedtothemotoraxis
Servomotorrotorinertia󰇛JM󰇜
100%