Chapter 6 – Additive Control
219
Firmware Version 3/4.31.37
(Note: If the Test Button is Enabled, the text ‘Hold Test Button To Inject Now!’ would appear instead of ‘Press
NEXT Key to Inject Now!’)
3. Place the test beaker to collect the additive injections and open the test port on the injector.
4. Press the NEXT key, or press the test button.
5. The first injection is made.
6. The number of meter pulses displays, as well as the delivered volume in gallons and in CCs (in parentheses).
7. Press the NEXT key again to get another injection. Continue to inject until you have enough volume in the
beaker to get a measurable reading.
PRE #1 ADTV #1 (Adtv 001 ) CALIBRATE
Press Next Key to Inject Now!
Injection: 1
Meter Pulses: 52
Delivered Volume: 0.020( 76cc)
Exit
PRE #1 ADTV #1 (Adtv 001 ) CALIBRATE
Press Next Key to Inject Now!
Injection: 0
Meter Pulses: 0
Delivered Volume: 0.000( 0cc)
Exit