E6582233
J-8
10
Ti tle
Communicati
on No.
Function Unit
Minimum
setting unit
Panel/Comm
unication
Adjustment range
Default
setting
User
setting
Reference
F311 0311 Reverse-run
prohibition
- - 0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
0
6.13.7
F312 0312 Random mode - - 0: Disabled
1: Automatic setting
0
6.12
F316 0316 Carrier frequency
control mode
selection
- - 0: Carrier frequency without reduction
1: Carrier frequency with automatic
reduction
2: Carrier frequency without reduction
Support 400V models
3: Carrier frequency with automatic
reduction
Support 400V models
3
F340 0340 Creeping time 1 s 0.01/0.01 0.00-10.00 0.00
6.14.1
F341 0341 Braking mode
selection
- -
0: Disabled
1-2: -
3: Horizontal operation
0
F343 0343 Torque bias input % 1/0.01 -250- +250 0
F344 0344 Factory specific
coefficient 3B
-
- - - * 1
F345 0345 Brake release time s 0.01/0.01 0.00-10.00 0.05
6.14.1
F346 0346 Creeping
frequency
Hz
0.1/0.01 f240 -20.0 3.0
F347 0347 Creeping time 2 s 0.01/0.01 0.00-10.00 0.10
F348 0348 Factory specific
coefficient 3C
-
- - - * 1
F359 0359 PID control waiting
time
s 1/1 0-2400 0
6.15
F360 0360 PID control - - 0: Disabled, 1: Enabled 0
F362 0362 Proportional gain - 0.01/0.01 0.01-100.0 0.30
F363 0363 Integral gain - 0.01/0.01 0.01-100.0 0.20
F366 0366 Differential gain - 0.01/0.01 0.00-2.55 0.00
F380 0380 PID
forward/reverse
characteristics
selection
- - 0: Forward
1: Reverse
0
F391 0391 Hysteresis for
lower-limit
frequency
operation
Hz 0.1/0.01 0.0- 0.2
6.9