E6582233
J-11
10
Title
Communicati
on No.
Function Unit
Minimum
setting unit
Panel/Comm
unication
Adjustment range
Default
setting
User
setting
Reference
F609 0609 Small current
detection
hysteresis
% 1/1 1-20 10 6.18.7
F610 0610 Small current
trip/alarm
selection
- - 0: Alarm only
1: Tripping
0
F611 0611 Small current
detection current
%
(A)
1/1 0-150 0
F612 0612 Small current
detection time
s 1/1 0-255 0
F613 0613 Detection of
output short-circuit
at start-up
- - 0: Each time (standard pulse)
1: Only one time after power on
(standard pulse)
2: Each time (short pulse)
3: Only one time after power on
(short pulse)
0 6.18.8
F615 0615 Over-torque
trip/alarm
selection
- - 0: Alarm only
1: Tripping
0 6.18.9
F616 0616 Over-torque
detection level
%
1/1 0 (disabled)
1-200
150
F618 0618 Over-torque
detection time
s 0.1/0.1 0.0-10.0 0.5
F619 0619 Over-torque
detection
hysteresis
% 1/1 0-100 10
F620 0620 Cooling fan
ON/OFF control
-
- 0: ON/OFF control
1: Always ON
0 6.18.10
F621 0621 Cumulative
operation time
alarm setting
100
hours
0.1/0.1
(=10
hours)
0.0-999.0 610.0 6.18.11
F626 0626 Over voltage stall
protection level
% 1/1 100-150 136 6.13.4
6.13.5
F627 0627 Undervoltage
trip/alarm
selection
- - 0: Alarm only
(detection level 64% or less)
1: Tripping
(detection level 64% or less)
2: Alarm only
(detection level 50% or less, input
AC reactor required)
0 6.18.12
F631 0631 Factory specific
coefficient 6A
- - - - * 1
F632 0632 Electronic-thermal
memory
- - 0: Disabled
1: Enabled
0 3.4
6.18.1
F633 0633 VI analog input
break detection
level
% 1/1 0: Disabled,
1-100
0 6.18.13
F634 0634 Annual average
ambient
temperature (parts
replacement
alarms)
- - 1: -10 to +10C
2: 11-20C
3: 21-30C
4: 31-40C
5: 41-50C
6: 51-60C
3 6.18.14
F648 0648 Number of starting
alarm
1000
0time
s
0.1/0.1 0.0-999.9 100.0 6.18.15
*1: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.