EasyManua.ls Logo

Toshiba TOSVERT VF-nC3E - Page 219

Toshiba TOSVERT VF-nC3E
252 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6582233
J-12
10
Output parameters
Ti tle
Communicati
on No.
Function Unit
Minimum
setting unit
Panel/Comm
unication
Adjustment range
Default
setting
User
setting
Reference

F669 0669 Logic output/pulse
train output
selection (OUT)
- - 0: Logic output
1: Pulse train output
0 6.19.1

F676 0676 Pulse train output
function selection
(OUT)
- -
0: Output frequency
1: Output current
2: Frequency reference
3: Input voltage (DC detection)
4: Output voltage (command value)
5 to 11: -
12: Frequency setting value (after
compensation)
13: VI input value
14: -
15: Fixed output 1 (output current
100% equivalent)
16: Fixed output 2 (output current
50% equivalent)
17: Fixed output 3
(Other than the output current)
18: RS485 Communication data
19 to 22: -
0

F677 0677 Maximum numbers
of pulse train
kpps 0.01/0.01 0.50-1.60 0.80

F678 0678 Factory specific
coefficient 6B
- - - -
* 1

F681 0681 Analog output
signal selection
- - 0: Meter option (0 to 1 mA)
1: Current (0 to 20 mA) output
2: Voltage (0 to 10 V) output
0
6.19.2

F684 0684 Factory specific
coefficient 6C
- - - -
* 1

F691 0691 Inclination
characteristic of
analog output
- - 0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
1 6.19.2

F692 0692 Analog output bias % 0.1/0.1 -1.0+100.0 0

F693 0693 Factory specific
coefficient 6D
- - - - * 1
*: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
Operation panel parameters
Ti tle
Communicati
on No.
Function Unit
Minimum
setting unit
Panel/Comm
unication
Adjustment range
Default
setting
User
setting
Reference

F700 0700
Parameter write
protection
selection
- - 0: Permitted
1: Prohibited (Panel and extension
panel)
2: Prohibited (1 + RS485
communication)
0 6.20.1

F701 0701
Current/voltage
unit selection
- - 0: %
1: A (ampere)/V (volt)
0 6.20.2

F702 0702
Free unit display
scale
Time
s
0.01/0.01 0.00: Disabled (display of frequency)
0.01-200.0
0.00 6.20.3

F707 0707
Free step
(1-step rotation of
setting dial)
Hz 0.01/0.01 0.00: Automatic
0.01-
0.00 6.20.4

Table of Contents