5 SETTING OF FUNCTIONS
45
SETTING OF FUNCTIONS
Chapter
5
HI limit / LO limit / HH limit / LL limit
How to set
Hysteresis
The hysteresis value may be determined so as to allow a margin for timing the turning off of the HI-
LO limit comparison. Normally, it is turned on when the indicated value exceeds the HI limit and is
turned off when the indicated value falls below it. However, by setting the hysteresis, it is turned off
when the indicated value falls below the HI limit further lowered by the hysteresis value.
This function is effective to prevent chattering in such a case where signals fluctuate (vibrate)
subtly.
Comparison conditions
- HI limit
ON condition: indicated valueHI limit value
OFF condition: indicated value(HI limit value-hysteresis value)
- LO limit
ON condition: indicated valueLO limit value
OFF condition: indicated value(LO limit value+hysteresis value)
- HH limit
ON condition: indicated valueHH limit value
OFF condition: indicated value(HH limit value-hysteresis value)
- LL limit
ON condition: indicated valueLL limit value
OFF condition: indicated value(LL limit value+hysteresis value)
Setting range: 0 - 9999
How to set
SET. Comp. Setting Page 1
→→
Work Setting
Simple setting call
Press any of the [HH], [HI], [LO] and [LL] buttons at the bottom of the indicated
value display screen to go direct to the entry screen.
SET. Comp. Setting Page 1
→→
Work Setting
Hysteresis setting value is common to all HI limit value.