92
8 SUPPLEMENTS
92
SUPPLEMENTS
Chapter
8
8-5. Setting Item List
■Work setting Comparison setting (WORK0 to WORK15)
Protect ○:Work Setting Protect, ◎:System Setting Protect, ●:Calibration Protect, レ:Expansion Protect
Memory S:SRAM, N:NOVRAM
*
1 0: H4/L0 1: H3/L1 2: H2/L2 3: H1/L3 4: H0/L4
■Work setting Hold setting (WORK0 to WORK15)
-Sample hold-
-Peak hold or Valley hold, and Section setting; Level-
-Average hold-
-Inflection Point hold-
Page No. Item Initial value Setting range Memory Protect
1
1 HH Limit 8000
- 99999 to 99999
S
○
2 HI Limit 6000
- 99999 to 99999
S
○
3 LO Limit 4000
- 99999 to 99999
S
○
4 LL Limit 2000
- 99999 to 99999
S
○
5 Hysteresis 0 0 to 9999 S
○
2
6
Alarm HI Limit 99999
- 99999 to 99999
S
○
7
Alarm LO Limit
- 99999 - 99999 to 99999
S
○
8 Near Zero 100 0 to 99999 S
○
9 Comparison Timing 0: ALL 0: ALL 1: MD 2: NZ 3: MD+NZ 4: HOLD S
○
10
Comparison Output
Selection
2: H2/L2 *1 S
○
Page No. Item Initial value Setting range Memory Protect
1
1 Hold Mode OFF
*2 *3
S
○
2 Hold Start Level 100
- 99999 to 99999
S
○
3 Section Time 1.000 sec 0.001 to 9.999 sec S
○
4
Level detection conditions 0 :Passed 0: Passed 1: Passed HI 2: Passed LO S
○
5
2
6 Sample Removal Value 0
- 999 to 999
S
○
7
8
9
10
2
6
Hold Stop Level 100
- 99999 to 99999
S
○
7
8
9
10
2
6 Average Sample Number 1 1 to 999 S
○
7
8
9
10
2
6 Inflection Minimum Slope 30 1 to 99999 S
○
7 Inflection Front Slope Time 200 10 to 990 (Front slope time + rear slope time < 1000) S
○
8 Inflection Rear Slope Time 200 10 to 990 (Front slope time + rear slope time < 1000) S
○
9 Inflection Removal Value 0
- 999 to 999
S
○
10
Detection Start Condition 0: Ext+Level
0: Ext+Level 1: Ext Only
S
○