56
5 SETTING OF FUNCTIONS
56
SETTING OF FUNCTIONS
Chapter
5
Inflection point hold
Detection starts when the SECTION signal is inputted and also the Level detection conditions is
met in comparison of the Hold Start Level and indicated value. Detection is performed as long as
the SECTION signal is ON.The Hold is released by turning on the T/H signal as a reset signal.
The H/E output signal is on between the instant when the hold starts and the instant when the T/H
signal is turned on. The next detection is started when the SECTION signal is turned on again even
if the T/H signal is not turned on.
If you want to perform detection simply by the SECTION signal without using the Hold Start
Level, set the Detection Start Condition to "External Only".
(Example) Inflection point hold
t1: A delay time between the instant
when the indicated value meets the
Hold Start Level under the Level
detection conditions and the instant
when detection starts.
t3: A minimum reset signal width
required for releasing the hold
1.0ms (min.)
Relative maximum, Relative minimum, Relative difference hold
The way of starting detection is the same as Inflection Point hold.
(Example) Relative maximum hold
t1: A delay time between the instant
when the indicated value exceeds the
Hold Start Level and the instant when
hold is detected.
t3: A minimum reset signal width
required for releasing the hold
1.0ms (min.)
Indicated
t3
Sensor Input Value
Detection
t
+
Hold Section
Fixed
SECTION
t1
Hold Start Level
T/H
H/E
OFF
ON
OFF
ON
OFF
ON
OFF
ON
HOLD
INF
ON
Blink
OFF
OFF
OFF
OFF
HOLD
Button
OFF
ON
ON*
ON*
Status Display
Status Display
Value
HI-LO Limit
Judging Output
*When it was not possible to hold correctly, both HOLD and INF status display are blinked.
t3
Sensor Input Value
Detection
t
+
Hold Section
Fixed
SECTION
t1
T/H
H/E
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
Blink ON*
OFF
OFF
OFF
OFF
HOLD
Button
OFF
ON
MAX
ON*
HOLD
Status Display
Status Display
Indicated
Value
Hold Start Level
HI-LO Limit
Judging Output
(Rel. Min: MIN)
(Rel. Dif : DIF)
*When it was not possible to hold correctly, both HOLD and MAX(MIN,DIF) status display are blinked.