113 
1. Speed feedback selection in full closed loop control 
Full  closed  loop  control  is  usually  set  to  "use  motor  encoder  speed  (P9-01.0  =  0).".  When 
connecting only the direct driving servo motor and the high-resolution grating ruler, please set it to "use 
grating ruler speed (P9-01.0 = 1)". 
2. Z-phase signal source 
P9-01.1 determines the z-phase source of the return to zero process. 
3. Servo pulse output 
Motor encoder phase ABZ output   
Grating ruler ABZ output waiting for positioning completion 
P9-01.2 determines the signal source of servo pulse output. 
5.9.3.4 Frequency division setting of mechanical side grating ruler 
Motor encoder feedback pulses 
per turn /Low 
Motor encoder feedback pulses 
per turn /High 
Grating ruler feedback pulses 
per turn /Low 
Grating ruler feedback pulses 
per turn /High 
 
1. Mechanical side grating scale frequency division 
=
Motor encoder feedback pulse per turn
External quadrature encoder pulse per turn 
=
P9-06*10000+P9-05
P9-08*10000+P9-07
 
Motor encoder feedback pulse per turn = P9-06*10000+ P9-05. When the set value = 0, the resolution 
of the encoder is set to the frequency division numerator. 
Grating ruler feedback pulse per turn = P9-08*10000+ P9-07, P9-08*10000+ P9-07. When the setting 
value = 0, set 10000 as the frequency division denominator. 
Input the frequency division ratio of external grating ruler completely, cannot input it after reducible 
division. 
2. In the  full closed-loop mode,  it is recommended that P0-11 and P0-12 be  set to 0, and  the 
electronic gear ratio of P0-13 and P0-14 is adopted. P0-11 and P0-12 can also be used on the premise 
that the frequency division of external grating ruler is correct, otherwise, E-236 will be alarmed. 
5.9.3.5 Alarm detection and clearing 
Alarm value of excessive 
deviation between motor and load 
position 
①  P9-02  deviation  setting  of  encoder  feedback  (position)  and  full  closed-loop  grating  scale 
feedback (load position).