Alarm List
Alarm Number (4000 to 4999)
Alarm List-914
YSF21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YSF21 board.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
3 Value of F_Src_Add is out of
range.
Setting error (1)Reset the alarm.
(2)If the alarm occurs again, please check the following F-Parameter
settings.
∙The value of F_Src_Add that is set to the safety PLC is in the range of
1-65534.
YSF21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YSF21 board.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
4 Value of F_WD_Time is 0. Setting error (1)Reset the alarm.
(2)If the alarm occurs again, please check the following F-Parameter
settings.
∙ The value of F_WD_Time that is set to the safety PLC is 1 or more.
YSF21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YSF21 board.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
5 Value of F_SIL is invalid. Setting error (1)Reset the alarm.
(2)If the alarm occurs again, please check the following.
∙ When setting up the safety the PLC, whether imported into SIEMENS
manufactured configuration tool(STEP 7) GSD file of CP1616 board
we offer.
YSF21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YSF21 board.
Alarm
Number
Alarm Name
Sub
Code
Meaning Cause Remedy