Alarm List
Alarm Number (1000 to 1999)
Alarm List-294
240 An error occurred in the start
process of the Ethernet
function Telnet (for onboard).
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
241 An error occurred in the start
process of the Ethernet
function Telnet (for expand).
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
1222 IP ADDRESS SET
FAIL(DHCP)
IP address could not be
obtained at DHCP.
Setting error (1)Check the following settings.
The DHCP server operation
The network status
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
1240 SAFETY FIELDBUS
SETTING ERROR
1 Machine Safety doesn't
correctly read the value of the
processing start wait time.
Data error (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the following parameter file in online
mode. Initialize the following parameter file in maintenance mode, and
then load the parameter file saved in the external memory device.
SD.PRM
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy