Alarm List
Alarm Number (1000 to 1999)
Alarm List-293
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
80 An error occurred in the basic
library initialization process of
the Ethernet function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
81 An error occurred in the
initialization process other
than basic library of the
Ethernet function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
100 An error occurred in the IP
address acquisition process in
the DHCP of the Ethernet
function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy