Alarm List
Alarm Number (1000 to 1999)
Alarm List-303
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
1310 CHARGE ERROR
(CONVERTER)
Module failure (converter) (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the converter.
Primary power failure Check if the primary power supply voltage does not drop with a tester,
etc.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
1311 A/D DETECTION
ERROR
(CONVERTER)
Module failure (converter) (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the converter.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
1312 ID ERROR
(CONVERTER)
Sub Code: Signifies the
converter in which the alarm
occurred
Module failure (converter) (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the converter.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
1313 COMMAND
ERROR(SERVO)
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
1314 VERIFY ERROR
(PARAMETER)
(SERVO)
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy