Alarm List
Alarm Number (1000 to 1999)
Alarm List-252
121 The segment_G process did
not complete within the time
set on the scheduling table.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
EAXA21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA21 board. Save the
CMOS.BIN before replace the board to be safe.
123 The general-purpose 2ms
process did not complete
within the time set on the
scheduling table.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
EAXA21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA21 board. Save the
CMOS.BIN before replace the board to be safe.
125 The dynamics calculation
process did not complete
within the time set on the
scheduling table.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
EAXA21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA21 board. Save the
CMOS.BIN before replace the board to be safe.
126 The dynamics compensation
process did not complete
within the time set on the
scheduling table.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
EAXA21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA21 board. Save the
CMOS.BIN before replace the board to be safe.
127 The CERF transmission
process did not complete
within the time set on the
scheduling table.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy