Alarm List
Alarm Number (1000 to 1999)
Alarm List-285
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
4 An error occurred in the
default gateway setting
process of the Ethernet
function.
Setting error (1)Check the following settings.
Default gateway of network in maintenance mode
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
5 An error occurred in the host
name setting process of the
Ethernet function.
Setting error (1)Check the following settings.
Server (host) of network in maintenance mode
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
YCP21 board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YCP21 board. Save the
CMOS.BIN before replace the board to be safe. Replace the YCP21
board, and then remove the CF from the failure YCP21 board to insert
it into the new YCP21 board.
6 An error occurred in the MAC
address getting process of the
Ethernet function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy