10-18
IM MV1000-01E
Target Channels
Press MENU and select Menu tab > Basic setting mode > Menu tab > Report >
Report settings
Overflow Data Handling
See page 10-5.
Settings
Report > Report select > 1, 2, 3, 4
Select the type of data to output as reports. The only data type that can be set more
than once is Off. You cannot set 1 to Off.
Setting Description
Off Does not generate reports.
Ave Outputs the average value.
Max Outputs the maximum value.
Min Outputs the minimum value.
Sum Outputs the sum.
Inst Outputs the instantaneous value.
Report > File type
Set this item to generate two types of reports such as daily and monthly reports.
Setting Description
Separate Saves each type of report to a separate file.
Combine Saves two types of report data to a single file.
Overflow Data Handling
Overow data is handled in the same way as it is in statistical computations (TLOG
and CLOG).
See section 10.1 for details.
Report set > Report kind
Select the type of report to be generated.
Setting Description
Hour Generates hourly reports.
Day Generates daily reports.
H+D Generates hourly and daily reports.
Day+Week Generates daily and weekly reports.
D+M Generates daily and monthly reports.
10.5 Generating Reports

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA MVAdvanced MV1000 Series and is the answer not in the manual?

YOKOGAWA MVAdvanced MV1000 Series Specifications

General IconGeneral
BrandYOKOGAWA
ModelMVAdvanced MV1000 Series
CategoryLaboratory Equipment
LanguageEnglish

Related product manuals