83
96.04 Macro select 2 =
Hand/Auto
3 =
Hand/PID
14 =
PID
15 =
Panel PID
16 =
PFC
22.71 Motor
potentiometer
function
0 = Disabled 0 = Disabled 0 = Disabled 0 = Disabled 0 = Disabled
22.73 Motor
potentiometer up
source
0 = Not
selected
0 = Not
selected
0 = Not
selected
0 = Not
selected
0 = Not
selected
22.74 Motor
potentiometer
down source
0 = Not
selected
0 = Not
selected
0 = Not
selected
0 = Not
selected
0 = Not
selected
28.11 Ext1 frequency
ref1
1 = AI1 scaled 1 = AI1 scaled 16 = PID 16 = PID 16 = PID
28.15 Ext1 frequency
ref2
2 = AI2 scaled 16 = PID 0 = Zero 0 = Zero 16 = PID
28.22 Constant
frequency sel1
0 = Not
selected
4 = DI3 5 = DI4 5 = DI4 0 = Not
selected
28.23 Constant
frequency sel2
0 = Not
selected
5 = DI4 0 = Not
selected
0 = Not
selected
0 =
Not
selected
28.71 Freq ramp set
selection
0 = Acc/Dec
time 1
0 = Acc/Dec
time 1
0 = Acc/Dec
time 1
0 = Acc/Dec
time 1
0 = Acc/Dec
time 1
40.07 Process PID
operation mode
0 = Off 2 = On when
drive running
2 = On when
drive running
2 = On when
drive running
2 = On when
drive running
40.16 Set 1 setpoint 1
source
11 = AI1
percent
11 = AI1
percent
11 = AI1
percent
13 = Control
panel (ref
11 = AI1
percent
40.17 Set 1 setpoint 2
source
0 = Not
selected
0 = Not
selected
2 = Internal
setpoint
0 = Not
selected
0 = Not
selected
40.19 Set 1 internal
setpoint sel1
0 = Not
selected
0 = Not
selected
3 = DI2 0 = Not
selected
0 = Not
selected
40.20 Set 1 internal
setpoint sel2
0 = Not
selected
0 = Not
selected
4 = DI3 0 = Not
selected
0 = Not
selected
40.32 Set 1 gain 1.00 1.00 1.00 1.00 2.50
40.33 Set 1 integration
time
60.0 60.0 60.0 60.0 3.0
76.21 PFC configuration 0=Off 0=Off 0=Off 0=Off 2=PFC
76.25 Number of motors 11112
76.27 Max number of
motors allowed
11112