Parameters 177
06.63 User status word 1
bit 3 sel
Selects a binary source whose status is shown as bit 3 of
06.50 User status word 1.
Magnetized
False 0. 0
True 1. 1
Magnetized Bit 1 of 06.17 Drive status word 2 (see page 168). 2
Other [bit] Source selection (see Terms and abbreviations on page 148). -
06.64 User status word 1
bit 4 sel
Selects a binary source whose status is shown as bit 4 of
06.50 User status word 1.
Run disable
False 0. 0
True 1. 1
Run disable Bit 5 of 06.18 Start inhibit status word (see page 169). 2
Other [bit] Source selection (see Terms and abbreviations on page 148). -
06.65 User status word 1
bit 5 sel
Selects a binary source whose status is shown as bit 5 of
06.50 User status word 1.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 148). -
06.66 User status word 1
bit 6 sel
Selects a binary source whose status is shown as bit 6 of
06.50 User status word 1.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 148). -
06.67 User status word 1
bit 7 sel
Selects a binary source whose status is shown as bit 7 of
06.50 User status word 1.
Identification
run done
False 0. 0
True 1. 1
Identification run
done
Bit 0 of 06.17 Drive status word 2 (see page 168). 2
Other [bit] Source selection (see Terms and abbreviations on page 148). -
06.68 User status word 1
bit 8 sel
Selects a binary source whose status is shown as bit 8 of
06.50 User status word 1.
Start
inhibition
False 0. 0
True 1. 1
Start inhibition Bit 7 of 06.18 Start inhibit status word (see page 169). 2
Other [bit] Source selection (see Terms and abbreviations on page 148). -
06.69 User status word 1
bit 9 sel
Selects a binary source whose status is shown as bit 9 of
06.50 User status word 1.
Limiting
False 0. 0
True 1. 1
Limiting Bit 7 of 06.16 Drive status word 1 (see page 167). 2
Other [bit] Source selection (see Terms and abbreviations on page 148). -
06.70 User status word 1
bit 10 sel
Selects a binary source whose status is shown as bit 10 of
06.50 User status word 1.
Torque
control
False 0. 0
No. Name/Value Description Def/FbEq16

Table of Contents

Other manuals for ABB ACS880-104

Related product manuals