Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.00 s / real32(Visible when 15.1 Module 2 type = FDIO-01)
See parameter 14.23 DI3 OFF delay.
DI3 OFF delay15.23
0.00 s / real32(Visible when 15.1 Module 2 type = FIO-01)
See parameter 14.23 DIO3 OFF delay.
DIO3 OFF delay15.23
Input / uint16(Visible when 15.1 Module 2 type = FIO-01)
See parameter 14.24 DIO4 function.
DIO4 function15.24
Not energized /
uint32
(Visible when 15.1 Module 2 type = FIO-01)
See parameter 14.26 DIO4 output source.
DIO4 output source15.26
- / real32(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.26 AI1 actual value.
AI1 actual value15.26
0.00 s / real32(Visible when 15.1 Module 2 type = FIO-01)
See parameter 14.27 DIO4 ON delay.
DIO4 ON delay15.27
- / real32(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.27 AI1 scaled value.
AI1 scaled value15.27
0.00 s / real32(Visible when 15.1 Module 2 type = FIO-01)
See parameter 14.28 DIO4 OFF delay.
DIO4 OFF delay15.28
- / real32(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.28 AI1 force data.
AI1 force data15.28
mA / uint16(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.29 AI1 HW switch position.
AI1 HW switch
position
15.29
mA / uint16(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.30 AI1 unit selection.
AI1 unit selection15.30
- / uint16(Visible when 15.1 Module 2 type = FDIO-01)
See parameter 14.31 RO status.
RO status15.31
- / uint16(Visible when 15.1 Module 2 type = FIO-01)
See parameter 14.31 RO status.
RO status15.31
1 ms / uint16(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.31 AI1 filter gain.
AI1 filter gain15.31
0.100 s / real32(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.32 AI1 filter time.
AI1 filter time15.32
0.000 mA or V /
real32
(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.33 AI1 min.
AI1 min15.33
Not energized /
uint32
(Visible when 15.1 Module 2 type = FDIO-01)
See parameter 14.34 RO1 source.
RO1 source15.34
Not energized /
uint32
(Visible when 15.1 Module 2 type = FIO-01)
See parameter 14.34 RO1 source.
RO1 source15.34
10.000 mA or V /
real32
(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.34 AI1 max.
AI1 max15.34
0.00 s / real32(Visible when 15.1 Module 2 type = FDIO-01)
See parameter 14.35 RO1 ON delay.
RO1 ON delay15.35
0.00 s / real32(Visible when 15.1 Module 2 type = FIO-01)
See parameter 14.35 RO1 ON delay.
RO1 ON delay15.35
0.000 / real32(Visible when 15.1 Module 2 type = FAIO-01)
See parameter 14.35 AI1 scaled at AI1 min.
AI1 scaled at AI1 min15.35