Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
34Control word bit 3 received from the active control
source.
Note:
If the drive is running in fieldbus control, switching
bit 3 off effectively removes both the start and
run enable signals.
In this case, the stop mode is determined by either
20.11 Run enable stop mode or 21.3 Stop mode,
whichever mode has higher priority. The order of
stop modes from highest to lowest priority is
Coast Torque limit Ramp.
In case the active source is the control panel, PC
tool or drive I/O, the run enable signal is always
on.
Active control
source MCW bit 3
See Terms and abbreviations (page 169).Other [bit]
Selected / uint32Selects the source for the start enable signal.
1 = Start enable.
With the signal switched off, any drive start command
is inhibited. (Switching the signal off while the drive is
running will not stop the drive.)
Note:
If a level-triggered start command is on when the
start enable signal switches on, the drive will start.
(An edgetriggered start signal must be cycled for
the drive to start.) See parameters 20.2 Ext1 start
trigger type, 20.7 Ext2 start trigger type and 20.29
Local start trigger type.
The warning that indicates a missing signal can
be suppressed using parameter 20.30 Enable
signals warning function.
See also parameter 20.12 Run enable 1 source.
Enable start
command
20.19
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO1 (11.2 DIO delayed status, bit
1).
DIO2
30DIIL input (10.2 DI delayed status, bit 15).DIIL
286 Parameters