Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Not selected / uint32When bit 0 of parameter 28.21 Constant frequency
function is 0 (Separate), selects a source that activates
constant frequency 2.
When bit 0 of parameter 28.21 Constant frequency
function is 1 (Packed), this parameter and parameters
28.22 Constant frequency sel1 and 28.24 Constant
frequency sel3 select three sources that are used to
activate constant frequencies.
See table at parameter 28.22 Constant frequency sel1.
For the selections, see parameter 28.22 Constant
frequency sel1.
Constant frequency
sel2
28.23
Not selected / uint32When bit 0 of parameter 28.21 Constant frequency
function is 0 (Separate), selects a source that activates
constant frequency 3.
When bit 0 of parameter 28.21 Constant frequency
function is 1 (Packed), this parameter and parameters
28.22 Constant frequency sel1 and 28.23 Constant
frequency sel2 select three sources that are used to
activate constant frequencies.
See table at parameter 28.22 Constant frequency sel1.
For the selections, see parameter 28.22 Constant
frequency sel1.
Constant frequency
sel3
28.24
0.00 Hz / real32Defines constant frequency 1 (the frequency the motor
will turn when constant frequency 1 is selected).
Constant frequency
1
28.26
- / -Constant frequency 1. For scaling, see parameter 46.2.-598.00 ... 598.00 Hz
0.00 Hz / real32Defines constant frequency 2.Constant frequency
2
28.27
- / -Constant frequency 2. For scaling, see parameter 46.2.-598.00 ... 598.00 Hz
0.00 Hz / real32Defines constant frequency 3.Constant frequency
3
28.28
- / -Constant frequency 3. For scaling, see parameter 46.2.-598.00 ... 598.00 Hz
0.00 Hz / real32Defines constant frequency 4.Constant frequency
4
28.29
- / -Constant frequency 4. For scaling, see parameter 46.2.-598.00 ... 598.00 Hz
0.00 Hz / real32Defines constant frequency 5.Constant frequency
5
28.30
- / -Constant frequency 5. For scaling, see parameter 46.2.-598.00 ... 598.00 Hz
0.00 Hz / real32Defines constant frequency 6.Constant frequency
6
28.31
- / -Constant frequency 6. For scaling, see parameter 46.2.-598.00 ... 598.00 Hz
0.00 Hz / real32Defines constant frequency 7.Constant frequency
7
28.32
- / -Constant frequency 7. For scaling, see parameter 46.2.-598.00 ... 598.00 Hz