Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = 1 s / 1 = 1 sMotor thermal time constant.100...10000 s
No action / uint16Selects the action taken when motor overload is
detected.
See section Motor overload protection (page 132).
Motor overload
action
35.56
0No action taken.No action
1Drive generates warning A783 Motor overload when
the motor is overloaded to the warning level, that is,
parameter 35.5 Motor overload level reaches value
88.0%.
Warning only
2Drive generates warning A783 Motor overload when
the motor is overloaded to the warning level, that is,
parameter 35.5 Motor overload level reaches value
88.0%.
Drive trips on fault 7122 Motor overload when the motor
is overloaded to the fault level, that is, parameter 35.5
Motor overload level reaches value 100.0%.
Warning and fault
Class 20 / uint16Defines the motor overload class to be used. The class
of protection is specified by the user as the time for
tripping at 7.2 times (IEC 60947-4-1) or 6 times (NEMA
ICS) the tripping level current.
See section Motor overload protection (page 132).
Motor overload class35.57
0Motor overload class 5.Class 5
1Motor overload class 10.Class 10
2Motor overload class 20.Class 20
3Motor overload class 30.Class 30
4Motor overload class 40.Class 40
0.0 % / real32Shows the calculated temperature of the motor cable.
See section Thermal protection of motor
cable (page 133).
102% = overtemperature warning (A480 Motor cable
overload)
106% = overtemperature fault (4000 Motor cable
overload)
This parameter is read-only.
Cable temperature35.60
1 = 1 % / 10 = 1 %Calculated temperature of motor cable.0.0 ... 200.0 %
10000.00 A / real32Specifies the continuous current of the motor cable
for the thermal protection function in the control
program.
WARNING!
The value entered in this parameter must be
limited according to all factors affecting the
loadability of the cable, such as ambient
temperature, cabling arrangement, and
shrouding. Refer to the technical data from the
cable manufacturer.
Cable nominal
current
35.61
1 = 1 A / 100 = 1 AContinuous current-carrying capacity of motor cable.0.00 ... 10000.00 A
408 Parameters