Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 s / uint16Specifies the thermal time of the motor cable for the
thermal protection function in the control program.
This value is defined as the time to reach 63% of the
nominal cable temperature when the cable is loaded
with nominal current (parameter 35.61 Cable nominal
current).
0 s = Thermal protection of motor cable disabled.
Refer to the technical data from the cable
manufacturer.
Cable current
Temperature rise
100%
100%
63%
Time
Time
Cable thermal time
Cable thermal rise
time
35.62
1 = 1 s / 1 = 1 s0 s Thermal protection of motor cable disabled.
1…50000 s Motor cable thermal time constant.
0...50000 s
Off, 06.16 b6 (95.20
b6) / uint32
Parameters 35.10035.106 configure a monitored
start/stop control logic for external equipment such
as a contactor controlled motor cooling fan.
This parameter selects the signal that starts and stops
the fan.
0 = Stop
1 = Start
The output controlling the fan contactor is to be
connected to parameter 35.105, bit 1. On and off delays
can be set for the fan by 35.101 and 35.102 respectively.
A feedback signal from the fan can be connected to an
input selected by 35.103; the loss of the feedback will
optionally trigger a warning or fault (see 35.104 and
35.106).
DOL starter control
source
35.100
00 (function disabled).Off
Parameters 409