What to doCause
Event name /
Aux. code
Code
(hex)
FEN
temperature
A782
Check that parameter 35.11
Temperature 1 source / 35.21
Error in temperature
measurement when temperature
sensor (KTY or PTC) connected Temperature 2 source setting
to encoder interface FEN-xx is
used.
corresponds to actual encoder
interface installation.
Check the settings of parameters
91.21 and 91.24. Check that the
Error in temperature
measurement when KTY sensor
corresponding module is
connected to encoder interface
FEN-01 is used.
activated in parameters
91.1191.14. Use parameter 91.10
Encoder parameter refresh to
validate any changes in the
settings.
FEN-01 does not support
temperature measurement with
KTY sensor. Use PTC sensor or
other encoder interface module.
Check for overloaded motor.Motor current is too high.Motor
overload
A783
Adjust the parameters used for the
motor overload function (35.5135.53)
and 35.5535.56.
Check that a brake resistor has been
connected.
Brake resistor broken or not
connected.
Brake resistorA791
Check the condition of the brake
resistor.
Stop drive. Let resistor cool down.Brake resistor temperature has
exceeded warning limit defined by
BR excess
temperature
A793
Check resistor overload protection
function settings (parameter group
43 Brake chopper).
parameter 43.12 Brake resistor
warning limit.
Check warning limit setting,
parameter 43.12 Brake resistor
warning limit.
Check that the resistor has been
dimensioned correctly.
Check that braking cycle meets
allowed limits.
One or more of the resistor data
settings (parameters 43.843.10) is
incorrect.
Brake resistor data has not been given.BR dataA794
The parameter is specified by the
auxiliary code.
Check value of 43.10.Resistance value too low.0000 0001
Check value of 43.8.Thermal time constant not given.0000 0002
Check value of 43.9.Maximum continuous power not
given.
0000 0003
Check the auxiliary code (format XXYY
ZZZZ). “XX” specifies the number of
Speed feedback configuration has
changed.
Speed
feedback
configuration
A797
the encoder interface module (01:
91.11/91.12, 02: 91.13/91.14, “YY”
specifies the encoder (01: 92 Encoder
1 configuration, 02: 93 Encoder 2
680 Fault tracing