Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
3 / uint16Specifies the slot (1…3) on the control unit of the drive
into which the interface module is installed.
Alternatively, specifies the node ID of the slot on an
FEA-03 extension adapter.
Module 2 location91.14
1 = 1 / 1 = 1Slot 1 = 1; Slot 2 = 2; Slot 3 = 3
4…254: Node ID of the slot on the FEA-03 extension
adapter
1...254
None / uint16Specifies the type of temperature sensor connected
to interface module 1. Note that the module must also
be activated by parameters 91.11 91.12.
Module 1 temp
sensor type
91.21
0None.None
1PTC. (The unit is ohms.)PTC
2KTY84. (The unit is selected by parameter 96.16 Unit
selection.)
KTY-84
3Pt1000 (The unit is selected by parameter 96.16 Unit
selection).
Note: Pt1000 sensor supports FEN-11 and FEN-31
encoder modules only.
Pt1000
1500 ms / real32Defines a filtering time for the temperature
measurement through interface module 1.
Module 1 temp filter
time
91.22
- / -Filtering time for temperature measurement.0...10000 ms
None / uint16Specifies the type of temperature sensor connected
to interface module 2. Note that the module must also
be activated by parameters 91.13 91.14.
Module 2 temp
sensor type
91.24
0None.None
1PTC. (The unit is ohms.)PTC
2KTY84. (The unit is selected by parameter 96.16 Unit
selection.)
KTY-84
3Pt1000 (The unit is selected by parameter 96.16 Unit
selection).
Note: Pt1000 sensor supports FEN-11 and FEN-31
encoder modules only.
Pt1000
1500 ms / real32Defines a filtering time for the temperature
measurement through interface 2.
Module 2 temp filter
time
91.25
- / -Filtering time for temperature measurement.0...10000 ms
Not selected / uint16Selects the encoder input on interface module 1 whose
signal is echoed by or emulated to the TTL output.
See also section Encoder support (page 92).
Module 1 TTL output
source
91.31
0TTL output not in use.Not selected
1Input 1 is echoed by or emulated to the TTL output.Module input 1
2Input 2 is echoed by or emulated to the TTL output.Module input 2
- / uint16Defines the number of TTL pulses per revolution for
encoder emulation output of interface module 1.
Module 1 emulation
pulses/rev
91.32