Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
0.0 / real32Defines the start limit for the sleep function when
parameter 40.41 Set 1 sleep mode is set to Internal.
Set 1 sleep level40.43
1 = 1 / 10 = 1Sleep start level.0.0 ... 32767.0
60.0 s / real32Defines a delay before the sleep function actually
becomes enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep condition
selected by parameter 40.41 Set 1 sleep mode becomes
true, and resets if the condition becomes false.
Set 1 sleep delay40.44
1 = 1 s / 10 = 1 sSleep start delay.0.0 ... 3600.0 s
0.0 s / real32Defines a boost time for the sleep boost step. See
parameter 40.46 Set 1 sleep boost step.
Set 1 sleep boost
time
40.45
1 = 1 s / 10 = 1 sSleep boost time.0.0 ... 3600.0 s
0.0 / real32When the drive is entering sleep mode, the process
setpoint is increased by this value for the time defined
by parameter 40.45 Set 1 sleep boost time.
If active, sleep boost is aborted when the drive wakes
up.
Set 1 sleep boost
step
40.46
1 = 1 / 10 = 1Sleep boost step.0.0 ... 32767.0
- / real32When 40.41 Set 1 sleep mode is set to Internal, this
parameter defines the wake-up level as deviation
between process setpoint and feedback. The unit is
selected by parameter 40.12 Set 1 unit selection.
When the deviation exceeds the value of this parameter,
and remains there for the duration of the wake-up delay
(40.48 Set 1 wake-up delay), the drive wakes up.
See also parameter 40.31 Set 1 deviation inversion.
Set 1 wake-up
deviation
40.47
1 = 1 rpm, % or Hz /
100 = 1 rpm, % or Hz
Wake-up level (as deviation between process setpoint
and feedback).
-32768.00 ...
32767.00 rpm, % or
Hz
0.50 s / real32Defines a wake-up delay for the sleep function to
prevent nuisance wake-ups. See parameter 40.47 Set
1 wake-up deviation.
The delay timer starts when the deviation exceeds the
wakeup level (40.47 Set 1 wake-up deviation), and resets
if the deviation falls below the wake-up level.
Set 1 wake-up delay40.48
430 Parameters