EasyManua.ls Logo

ABB ACS880 - Page 431

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = 1 s / 100 = 1 sWake-up delay.0.00 ... 60.00 s
Not selected / uint32Activates (or selects a source that activates) tracking
mode. In tracking mode, the value selected by
parameter 40.50 Set 1 tracking ref selection is
substituted for the PID controller output. See also
section Process PID control (page 109).
1 = Tracking mode enabled
Set 1 tracking mode40.49
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
Not selected / uint32Selects the value source for tracking mode. See
parameter 40.49 Set 1 tracking mode.
Set 1 tracking ref
selection
40.50
0None.Not selected
112.12 AI1 scaled value (page 226).AI1 scaled
212.22 AI2 scaled value (page 228).AI2 scaled
33.5 FB A reference 1 (page 179).FB A ref1
43.6 FB A reference 2 (page 179).FB A ref2
See Terms and abbreviations (page 169).Other [value]
Off / uint16Activates the trim function and selects between direct
and proportional trimming (or a combination of both).
With trimming, it is possible to apply a corrective factor
to the drive reference (setpoint). The output after
trimming is available as parameter 40.5 Process PID
trim output act.
See the control chain diagram on page 759.
Set 1 trim mode40.51
0The trim function is inactive.Off
1The trim function is active. The trimming factor is
relative to the maximum speed, torque or frequency;
the selection between these is made by parameter
40.52 Set 1 trim selection.
Direct
2The trim function is active. The trimming factor is
relative to the reference selected by parameter 40.53
Set 1 trimmed ref pointer.
Proportional
Parameters 431