Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
3The trim function is active. The trimming factor is a
combination of both Direct and Proportional modes;
the proportions of each are defined by parameter 40.54
Set 1 trim mix.
Combined
Torque / uint16Selects whether trimming is used for correcting the
speed, torque or frequency reference.
Set 1 trim selection40.52
1Torque reference trimming.Torque
2Speed reference trimming.Speed
3Frequency reference trimming.Frequency
Not selected / uint32Selects the signal source for the trim reference.Set 1 trimmed ref
pointer
40.53
0None.Not selected
112.12 AI1 scaled value (page 226).AI1 scaled
212.22 AI2 scaled value (page 228).AI2 scaled
33.5 FB A reference 1 (page 179).FB A ref1
43.6 FB A reference 2 (page 179).FB A ref2
See Terms and abbreviations (page 169).Other [value]
0.000 / real32When parameter 40.51 Set 1 trim mode is set to
Combined, defines the effect of direct and proportional
trim sources in the final trimming factor.
0.000 = 100% proportional
0.500 = 50% proportional, 50% direct
1.000 = 100% direct
Set 1 trim mix40.54
1 = 1 / 1000 = 1Trim mix.0.000 ... 1.000
1.000 / real32Defines a multiplier for the trimming factor. This value
is multiplied by the result of parameter 40.51 Set 1 trim
mode.
Consequently, the result of the multiplication is used
to multiply the result of parameter 40.56 Set 1 trim
source.
Set 1 trim adjust40.55
1 = 1 / 1000 = 1Multiplier for trimming factor.-100.000 ... 100.000
PID ref / uint16Selects the reference to be trimmed.Set 1 trim source40.56
1PID setpoint.PID ref
2PID controller output.PID output
Not selected / uint32Selects the source that determines whether process
PID parameter set 1 (parameters 40.07…40.56) or set
2 (group 41 Process PID set 2) is used.
0 = Process PID parameter set 1 in use
1 = Process PID parameter set 2 in use
PID set1/set2
selection
40.57
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
432 Parameters