Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.00 rpm / real32Defines a speed corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example,
with a setting of 500, the fieldbus reference range of
0…20000 would correspond to a speed of 500…[46.1]
rpm.
Note: This parameter is effective only with the ABB
Drives communication profile.
Speed ref zero
scaling
46.6
1 = 1 rpm / 100 = 1
rpm
Speed corresponding to minimum fieldbus reference.0.00 ... 30000.00
rpm
0.00 Hz / real32Defines a frequency corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example,
with a setting of 30, the fieldbus reference range of
0…20000 would correspond to a speed of 30…[46.2]
Hz.
Note: This parameter is effective only with the ABB
Drives communication profile.
Frequency ref zero
scaling
46.7
10 = 1 Hz / 100 = 1 HzFrequency corresponding to minimum fieldbus
reference.
0.00 ... 1000.00 Hz
500 ms / real32Defines a filter time for signals 1.1 Motor speed used,
1.2 Motor speed estimated, 1.4 Encoder 1 speed filtered
and 1.5 Encoder 2 speed filtered.
Filter time motor
speed
46.11
1 = 1 ms / 1 = 1 msMotor speed signal filter time.0...20000 ms
500 ms / real32Defines a filter time for signal 1.6 Output frequency.Filter time output
frequency
46.12
1 = 1 ms / 1 = 1 msOutput frequency signal filter time.0...20000 ms
100 ms / real32Defines a filter time for signal 1.10 Motor torque.Filter time motor
torque
46.13
1 = 1 ms / 1 = 1 msMotor torque signal filter time.0...20000 ms
100 ms / real32Defines a filter time for signal 1.14 Output power.Filter time power
out
46.14
1 = 1 ms / 1 = 1 msOutput power signal filter time.0...20000 ms
452 Parameters