Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
False / uint32Changing the value of (or the source selected by) this
parameter from 0 to 1 reboots the optional FSO-xx
safety functions module.
Note: The value does not revert to 0 automatically.
FSO reboot96.9
00.False
11.True
See Terms and abbreviations (page 169).Other [bit]
n/a / uint16Shows the status of the user parameter sets.
Note: This parameter is read-only.
See also section User parameter sets (page 140).
User set status96.10
0No user parameter sets have been saved.n/a
1A user set is being loaded.Loading
2A user set is being saved.Saving
3Invalid parameter set.Faulted
4User set 1 has been loaded.User set 1
5User set 2 has been loaded.User set 2
6User set 3 has been loaded.User set 3
7User set 4 has been loaded.User set 4
No action / uint16Enables the saving and restoring of up to four custom
sets of parameter settings. See section User parameter
sets (page 140).
The set that was in use before powering down the drive
is in use after the next power-up.
Note: Hardware configuration settings such as I/O
extension module, fieldbus and encoder configuration
parameters (groups 14…16, 51…56, 58 and 92…93, and
parameters 50.1 and 50.31), and forced input/output
values (such as 10.3 and 10.4) are not included in user
parameter sets.
Note: Parameter changes made after loading a set are
not automatically stored – they must be saved using
this parameter.
Note: If no sets have been saved, attempting to load a
set will create all sets from the currently active
parameter settings.
Note: Switching between sets is only possible with the
drive stopped.
User set save/load96.11
0Load or save operation complete; normal operation.No action
1Load user parameter set using parameters 96.12 and
96.13.
User set I/O mode
2Load user parameter set 1.Load set 1
606 Parameters