Parameters and firmware blocks
115
12.13 DI INVERT MASK FW block: DI (see above)
Inverts status of digital inputs as reported by 2.01 DI STATUS. For example, a value of 0b000100
inverts the status of DI3 in the signal.
0b000000…0b111111 DI status inversion mask.
12.14 DIO2 F MAX FW block: DIO2 (see above)
Defines the maximum value for frequency input (when 12.02 DIO2 CONF is set to (2) FREQ INPUT).
3…32768 Hz Maximum DIO2 input frequency.
12.15 DIO2 F MIN FW block: DIO2 (see above)
Defines the minimum value for frequency input (when 12.02 DIO2 CONF is set to (2) FREQ INPUT).
3…32768 Hz Minimum DIO2 input frequency.
12.16 DIO2 F MAX SCALE FW block: DIO2 (see above)
Defines the real value that corresponds to the maximum frequency input value defined by
parameter 12.14 DIO2 F MAX.
-32768…32768 Real value corresponding to value of parameter 12.14.
12.17 DIO2 F MIN SCALE FW block: DIO2 (see above)
Defines the real value that corresponds to the minimum frequency input value defined by
parameter 12.15 DIO2 F MIN. See parameter 12.16 DIO2 F MAX SCALE.
-32768…32768 Real value corresponding to value of parameter 12.15.
12.14
12.15
12.14
12.15
12.1712.1612.1612.17
DIO2 (real)
DIO2 (Hz)
DIO2 (real)
DIO2 (Hz)

Table of Contents