Parameters and firmware blocks
157
-32768…32768 Upper limit for supervision 1.
33.04 SUPERV1 LIM LO FW block: SUPERVISION (see above)
Sets the lower limit for supervision 1. See parameter 33.01 SUPERV1 FUNC.
-32768…32768 Lower limit for supervision 1.
33.05 SUPERV2 FUNC FW block: SUPERVISION (see above)
Selects the mode of supervision 2.
(0) DISABLED Supervision 2 not in use.
(1) LOW When the signal selected by parameter 33.06 SUPERV2 ACT falls
below the value of parameter 33.08 SUPERV2 LIM LO, bit 1 of 6.14
SUPERV STATUS is activated.
(2) HIGH When the signal selected by parameter 33.06 SUPERV2 ACT
exceeds the value of parameter 33.07 SUPERV2 LIM HI, bit 1 of 6.14
SUPERV STATUS is activated.
(3) ABS LOW When the absolute value of the signal selected by parameter 33.06
SUPERV2 ACT falls below the value of parameter 33.08 SUPERV2
LIM LO, bit 1 of 6.14 SUPERV STATUS is activated.
(4) ABS HIGH When the absolute value of the signal selected by parameter 33.06
SUPERV2 ACT exceeds the value of parameter 33.07 SUPERV2 LIM
HI, bit 1 of 6.14 SUPERV STATUS is activated.
33.06 SUPERV2 ACT FW block: SUPERVISION (see above)
Selects the signal to be monitored by supervision 2. See parameter 33.05 SUPERV2 FUNC.
Value pointer: Group and index
33.07 SUPERV2 LIM HI FW block: SUPERVISION (see above)
Sets the upper limit for supervision 2. See parameter 33.05 SUPERV2 FUNC.
-32768…32768 Upper limit for supervision 2.
33.08 SUPERV2 LIM LO FW block: SUPERVISION (see above)
Sets the lower limit for supervision 2. See parameter 33.05 SUPERV2 FUNC.
-32768…32768 Lower limit for supervision 2.
33.09 SUPERV3 FUNC FW block: SUPERVISION (see above)
Selects the mode of supervision 3.
(0) DISABLED Supervision 3 not in use.
(1) LOW When the signal selected by parameter 33.10 SUPERV3 ACT falls
below the value of parameter 33.12 SUPERV3 LIM LO, bit 2 of 6.14
SUPERV STATUS is activated.