Parameter data
254
12.16 DIO2 F MAX SCALE REAL -32768…
32768
- 1 = 1 10 ms 16 1500 115
12.17 DIO2 F MIN SCALE REAL -32768…
32768
- 1 = 1 10 ms 16 0 115
13 ANALOGUE INPUTS
13.01 AI1 FILT TIME REAL 0…30 s 1 = 1000 10 ms 16 0 116
13.02 AI1 MAX REAL -11…11/
-22…22
V or
mA
1 = 1000 10 ms 16 10 116
13.03 AI1 MIN REAL -11…11/
-22…22
V or
mA
1 = 1000 10 ms 16 -10 117
13.04 AI1 MAX SCALE REAL -32768…
32767
- 1 = 1000 10 ms 32 1500 117
13.05 AI1 MIN SCALE REAL -32768…
32767
- 1 = 1000 10 ms 32 -1500 117
13.06 AI2 FILT TIME REAL 0…30 s 1 = 1000 10 ms 16 0 117
13.07 AI2 MAX REAL -11…11/
-22…22
V or
mA
1 = 1000 10 ms 16 10 117
13.08 AI2 MIN REAL -11…11/
-22…22
V or
mA
1 = 1000 10 ms 16 -10 118
13.09 AI2 MAX SCALE REAL -32768…
32767
- 1 = 1000 10 ms 32 100 118
13.10 AI2 MIN SCALE REAL -32768…
32767
- 1 = 1000 10 ms 32 -100 118
13.11 AITUNE enum 0…4 - 1 = 1 10 ms 16 0 118
13.12 AI SUPERVISION enum 0…3 - 1 = 1 2 ms 16 0 119
13.13 AI SUPERVIS ACT UINT32 0000…
1111
-1 = 12 ms32 0 119
15 ANALOGUE
OUTPUTS
15.01 AO1 PTR Val pointer - - 32 P.01.05 120
15.02 AO1 FILT TIME REAL 0…30 s 1 = 1000 10 ms 16 0.1 120
15.03 AO1 MAX REAL 0…22.7 mA 1 = 1000 10 ms 16 20 120
15.04 AO1 MIN REAL 0…22.7 mA 1 = 1000 10 ms 16 4 121
15.05 AO1 MAX SCALE REAL -32768…
32767
- 1 = 1000 10 ms 32 100 121
15.06 AO1 MIN SCALE REAL -32768…
32767
- 1 = 1000 10 ms 32 0 121
15.07 AO2 PTR Val pointer - - 32 P.01.02 121
15.08 AO2 FILT TIME REAL 0…30 s 1 = 1000 10 ms 16 0.1 121
15.09 AO2 MAX REAL -10…10 V 1 = 1000 10 ms 16 10 122
15.10 AO2 MIN REAL -10…10 V 1 = 1000 10 ms 16 -10 122
15.11 AO2 MAX SCALE REAL -32768…
32767
- 1 = 1000 10 ms 32 100 122
15.12 AO2 MIN SCALE REAL -32768…
32767
- 1 = 1000 10 ms 32 -100 122
16 SYSTEM
16.01 LOCAL LOCK Bit pointer - 2 ms 32 C.False 123
16.02 PARAMETER LOCK enum 0…2 - 1 = 1 2 ms 16 1 123
Index Parameter Type Range Unit FbEq Update
time
Data
len.
Def PT Save
PF
Page
no.

Table of Contents

Other manuals for ABB ACSM1