Drive control and features
70
Rising edge of encoder DI1 (proximity switch signal) is detected at the first mark
of the belt. Position 0 mm is stored to signal 4.03 PROBE1 POS MEAS.
Falling edge of encoder DI2 (proximity switch signal) is detected at the second
mark of the belt. Position 40 mm is stored to signal 4.04 PROBE2 POS MEAS.
The reference distance between the marks is 60 mm and the measured distance
between the marks is 40 mm, thus the error is 20 mm:
(62.18 PROBE2 POS - 62.16 PROBE1 POS) - (4.04 PROBE2 POS MEAS - 4.03
PROBE1 POS MEAS)] = (60 - 0) - (40 - 0) = 20 mm
The error is stored to 4.18 SYNC ERROR:
Actual position of the encoder 1.12 POS ACT is corrected according to 4.18 SYNC
ERROR using positioning parameter and dynamic limiter settings.
Note: Only after the active correction is finished is the next position latching enabled.
62.18 PROBE2 POS 0.060 m (=60 mm) Reference position for actual position probe 2
Parameter Setting Information
t
t
t
t
1.01 SPEED ACT
1.12 POS ACT
Encoder DI1
Encoder DI2
POSITION DERIVATION
MEASURED POSITION DIFFERENCE