8.3 CS3 STANDARD DISPLAYS
Loading CS3 preconfigures the System Module display list for five displays. The five displays are
listed in Table 8-2 with appropriate reference sections, figure numbers, and configuration tables. A
configuration table is not listed for the Ratio Controller Single Loop CON0 display, as that informa-
tion is provided in this section. To configure the Single Loop CON0 (Ratio) with Horizontal Trend,
Parameter, and System Status displays, reference the Section 4 and Section 5 information listed in
the table.
Table 8-2. CS3 Standard Displays
Title
See
Section
Section 4
Figure
Section 5
Table
Ratio Controller (Point Display 3, CDM = 3) 4.3 and
4.3.4
4-6
Single Loop with Horizontal Trend (Ratio) 4.5 4-10 sheet 2 5-9
Parameter Module 0 - PID datapoints 4.6 4-11 5-11
Parameter Module 1- Alarm Limits 4.6 4-11 5-11
System Status 4.2 4-2 5-15
8.4 CS3 DATAPOINT CONFIGURATION SELECTIONS
See Figure 8-2 and Table 8-3 to configure datapoints for CS3 - Ratio (PID) Controller.
Table 8-3 also lists the Section 5 modules that can be referenced for more detailed definitions of
the datapoints when required.
A datapoint does not have to be configured if the default value
listed in Table 8-3 is appropriate for the process application.
Loading CS3 initializes the Engi-
neering Span (C257) to 100 for AI1 (Wild Variable). Also, the CON0 Display Mode (B339) is set to
3; the CON0 Setpoint Mode (B338) is set to 1; and datapoint C081 (Math B - K3) is set to 1.0.
Section 8. CS3 - Ratio (PID) Controller
8-3