EasyManua.ls Logo

ABB ControlIT 53MC5000 - Table 14-2. CS40 Standard Displays

ABB ControlIT 53MC5000
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 14-1. CS40 Control Signals
Control
Signal Definition
Cord
Set
ITB
Rear
Term
Board
Signal
DO1 - #2
Secondary
Process
Alarms
This contact is closed when the #2 Secondary
Process Variable value is not within the C211
and C212 datapoint values (#2 Secondary
Alarm Limits 1 and 2); otherwise, the contact is
open.
TB2-7 (+)
TB2-8 (-)
18 (+)
17 (-)
DO1
PC
14.3 CS40 STANDARD DISPLAYS
Loading CS40 preconfigures the System Module display list for ten displays. The ten displays are
listed in Table 14-2 with appropriate reference sections, figure numbers, and configuration tables.
A configuration table is not listed for the Four Loop CON0 - CON3 display, as that information is
provided in this section. To configure the Horizontal Trend, System Status, and Status Module dis-
plays, reference the Section 4 and Section 5 information listed in the table. The Alarm Summary
display does not have to be configured; however, it is described and illustrated in Section 4.
Table 14-2. CS40 Standard Displays
Title
See
Section
Section 4
Figure
Section 5
Table
Four Loop CON0 - CON3 4.10 4-15
Single Loop CON0 with Horizontal Trend 4.5 4-10 sheet 2 5-9 and 5-12
Single Loop CON1 with Horizontal Trend 4.5 4-10 sheet 2 5-9 and 5-12
Single Loop CON2 with Horizontal Trend 4.5 4-10 sheet 2 5-9 and 5-12
Single Loop CON3 with Horizontal Trend 4.5 4-10 sheet 2 5-9 and 5-12
Alarm Summary 4.1 4-1
System Status 4.2 4-2 5-15
Status Module 0 4.7 4-12 5-10
Status Module 1 4.7 4-12 5-10
Four Loop CON0 - CON3 4.10 4-15
14.4 CS40 DATAPOINT CONFIGURATION SELECTIONS
See Figure 14-2 and Table 14-3 to configure datapoints for CS40 - Dual Two Loop Cascade Con-
troller. Table 14-3 also lists the Section 5 modules that can be referenced for more detailed defini-
tions of the datapoints when required.
A datapoint does not have to be configured if the
default value listed in Table 14-3 is appropriate for the process application.
Loading CS40 in-
itializes the Engineering Spans to 100 for AIs 1-3 (C257, C258, and C259). Also, C076 (Math A -
K1) is set to 1.0, C077 (Math A - K2) is set to -1.0, C085 (Math D - K1) is set to 1.0, and C086
(Math D - K2) is set to -1.0. The CON0
OUT and CON1
OUT signals, which are the secondary set-
point inputs, must be properly scaled by configuring datapoints C184 (B1) and C185 (K1) for the #1
Secondary Control Output; and by configuring C220 (B1) and C221 (K1) for the #2 Secondary Con-
trol Output. These datapoints are listed in Table 14-3 under their respective CON
OUT Datapoints.
2 of 2
Section 14. CS40 - Dual Two Loop Cascade Controller
14-3

Table of Contents

Related product manuals