EasyManua.ls Logo

ABB ControlIT 53MC5000 - 11.0 CS20 - Two Loop Controller; 11.1 CS20 - Two Loop Controller

ABB ControlIT 53MC5000
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.0 CS20 - TWO LOOP CONTROLLER
11.1 CS20 - TWO LOOP CONTROLLER
A two loop 53MC5000 Controller is configured at the factory for CS20 operation to provide the
standard displays listed in Table 11-2 and the default datapoint settings listed in Table 11-3. As a
Two Loop (PID) Controller, each loop Proportional Band is set at 100%; the Process Variables AI0-
1 are scaled 0-100% for linear 4-20 mA input signals; and AO0-1 are set as reverse action (PV
above setpoint causes decreasing value) control signals over a 4-20 mA signalling range. These
settings may be altered and additional Control Strategy 20 (CS20) functions can be activated as ne-
cessitated by the process application. The Two Loop Controller provides two identical standard
PID controllers with both control loops fully independent of each other. The input/output signals for
the two control loops are identical: Process Variable (PV), Remote Setpoint, Remote Setpoint En-
able, Control Output, and Process Alarms.
Just as with the standard Single Loop (PID) Controller,
only the Process Variable and Control Output of each loop are required for control purposes; the
other signals do not have to be connected or configured
. Each loop calculates an output from the
difference between its Process Variable feedback signal sent from a Field Transmitter (FT) (e.g,
flow meter) and its setpoint (SP) value. After the output is calculated, it is applied to a final control
loop element (e.g, valve) to restore process flow to the loop setpoint value.
Validate the controller
model number to ensure it has the necessary two loop hardware capabilities.
A typical low-resolu-
tion display Two Loop Controller process application is illustrated in Figure 11-1.
Figure 11-1. Typical CS20 Two Loop Controller Application
PUMP
VALVE
LOOP 1
PUMP
VALVE
LOOP 2
FT
AI2 - REMOTE SETPOINT LOOP 1
AI3 - REMOTE SETPOINT LOOP 2
DI0 - REMOTE ENABLE LOOP 1
(CLOSED CONTACT)
DI1 - REMOTE ENABLE LOOP 2
(CLOSED CONTACT)
AI1 - PROCESS
VARIABLE LOOP 2
AI0 - PROCESS
VARIABLE LOOP 1
DO0 - PROCESS ALARMS LOOP 1
DO1 - PROCESS ALARMS LOOP 2
AO1 - CONTROL
OUTPUT LOOP 2
AO0 - CONTROL
OUTPUT LOOP 1
FT
Section 11. CS20 - Two Loop Controller
11-1

Table of Contents

Related product manuals