EasyManua.ls Logo

ABB ControlIT 53MC5000 - Table 15-2. CS41 Standard Displays

ABB ControlIT 53MC5000
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 15-1. CS41 Control Signals
Control
Signal Definition
Cord
Set
ITB
Rear
Term
Board
Signal
CCO2 -
Process Alarms
Loop 3
This contact is closed when the Loop 3 PV
value is not within Alarm Limits 1 and 2 (C175
and C176); otherwise, the contact is open.
6DI/4DO
ITB
TB2
TB2-1 (+)
TB2-2 (-)
CCO2+
CC02-
CCO3 -
Process Alarms
Loop 4
This contact is closed when the Loop 4 PV
value is not within Alarm Limits 1 and 2 (C211
and C212); otherwise, the contact is open.
6DI/4DO
ITB
TB2
TB2-3 (+)
TB2-4 (-)
CCO3+
CC03-
15.3 CS41 STANDARD DISPLAYS
Loading CS41 preconfigures the System Module display list for ten displays. The ten displays are
listed in Table 15-2 with appropriate reference sections, figure numbers, and configuration tables.
A configuration table is not listed for the Four Loop CON0 - CON3 display, as that information is
provided in this section. To configure the Horizontal Trend, System Status, and Status Module dis-
plays, reference the Section 4 and Section 5 information listed in the table. The Alarm Summary
display does not have to be configured; however, it is described and illustrated in Section 4.
Table 15-2. CS41 Standard Displays
Title
See
Section
Section 4
Figure
Section 5
Table
Four Loop CON0 - CON3 4.10 4-15
Single Loop CON0 with Horizontal Trend 4.5 4-10 sheet 2 5-9 and 5-12
Single Loop CON1 with Horizontal Trend 4.5 4-10 sheet 2 5-9 and 5-12
Single Loop CON2 with Horizontal Trend 4.5 4-10 sheet 2 5-9 and 5-12
Single Loop CON3 with Horizontal Trend 4.5 4-10 sheet 2 5-9 and 5-12
Alarm Summary 4.1 4-1
System Status 4.2 4-2 5-15
Status Module 0 4.7 4-12 5-10
Status Module 1 4.7 4-12 5-10
Four Loop CON0 - CON3 4.10 4-15
15.4 CS41 DATAPOINT CONFIGURATION SELECTIONS
See Figure 15-2 and Table 15-3 to configure datapoints for CS41 - Four Loop Controller.
Table 15-3 also lists the Section 5 modules that can be referenced for more detailed definitions of
the datapoints when required.
A datapoint does not have to be configured if the default value
listed in Table 15-3 is appropriate for the process application.
Loading CS41 initializes the En-
gineering Spans AI1-7 to 100 (C257 - C263). When an open contact is present on CCI4, CCI5,
CCI6, or CCI7 (Force Fallback Loops 1-4), the loops output and setpoint are forced to fallback val-
ues contained in the CON0-3 modules Output Track Value (OTV) and Setpoint Track Value (STV)
datapoints (OTV = C129, C165, C201, and C237; STV = C128, C164, C200, and C236) only if the
CON0-3 modules Output Track Enable (OTE) and Setpoint Track Enable (STE) datapoints are con-
figured to 1 (OTE = L119, L143, L167, and L191; STE = L118, L142, L166, and L190).
3 of 3
53MC5000 Process Control Station
15-4

Table of Contents

Related product manuals