EasyManua.ls Logo

ABB ControlIT 53MC5000 - Page 272

ABB ControlIT 53MC5000
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 14-3. CS40 Dual Two Loop Cascade Controller Datapoints
Data-
point Table Module Title and Function
De-
fault
CON1
OUT (Setpoint from Loop 2 to Loop 4) (Cont)
C147 5-9 CON1 Manual Reset - It determines output valve position when the
controller Loop 2 is in Auto and the error = 0. It is mutually
exclusive with Reset Time.
50
L138 5-9 CON1 Auto Enable - Output is from the PID algorithm when set to 1
and the A/M push button is in Auto.
1
C115 5-9 CON1 Controller Span - Enter a value, that when added to the
Loop 2 Control Lower Range value, will produce the Control
upper range value in engineering units.
100
C152 5-9 CON1 Controller Lower Range - Enter a value that represents in
engineering units the Loop 2 Control lower range value.
0
AO1 - #2 Secondary Control Output (Loop 4)
L473 5-5 AO1 0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
Enter a value to match the Loop 4 output valve requirements.
0
L192 5-9 CON3 Manual Fallback Disable - 0 = always power up Loop 4 in
manual; 1 = auto/manual selector unchanged at power up.
0
L194 5-9 CON3 Hard Manual Limit - 1 = apply output limits to the final output
of the Loop 4 Auto-Manual Generator. Affects both the
manual push buttons and the controllers result. 0 = do not
apply limits.
1
C217 5-9 CON3 Output High Limit - Sets maximum Loop 4 output signal
value in engineering units.
100
C218 5-9 CON3 Output Low Limit - Sets minimum Loop 4 output signal value
in engineering units.
0
C226 5-9 CON3 Output Slew Rate - It is a rate limit applied to the output
value. When configured to a non-zero value, the output from
the Loop 4 Auto-Selector is only allowed to change by this
amount each scan time. A zero disables output slewing. It
does not affect manual operation.
0
CON 3 #2 Secondary Control Output (LOOP 4) Related Datapoints
C214 5-9 CON3 Proportional Band - Is the percent of error required to move
the Loop 4 output full scale for proportional action.
100
C215 5-9 CON3 Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.
0
C216 5-9 CON3 Rate Time - Represents the minutes proportional action is
advanced.
0
C219 5-9 CON3 Manual Reset - It determines output valve position when the
controller Loop 4 is in Auto and the error = 0. It is mutually
exclusive with Reset Time.
50
L178 5-9 CON3 Reverse Switch - 0 = Loop 4 output
if PV
; 1 = Loop 4
output
if PV
.
1
L186 5-9 CON3 Auto Enable - Output is from the PID algorithm when set to 1
and the A/M push button is in Auto.
1
C221 5-9 CON3 Remote Setpoint Ratio (K1) - See Remote Setpoint Bias (B1)
above.
1
5 of 7
Section 14. CS40 - Dual Two Loop Cascade Controller
14-11

Table of Contents

Related product manuals