EasyManua.ls Logo

ABB ControlIT 53MC5000 - Page 308

ABB ControlIT 53MC5000
406 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17.6 ABORTING THE EASY-TUNE SEQUENCE
If the EASY-TUNE sequence is active and the controller output is deliberately changed, the se-
quence will be aborted. The original controller output and Manual or Auto mode will be restored.
Datapoint B387, EASY-TUNE Status, will be set to
54
.
If the EASY-TUNE sequence is active and datapoint L521, EASY-TUNE Abort Switch, is set to
1
,
the sequence is immediately aborted. The original controller output and Manual or Auto mode will
be restored. Datapoint B387, EASY-TUNE Status, will be set to
60
.
17.7 EASY-TUNE SEQUENCE COMPLETION
Upon successful completion of the EASY-TUNE sequence, the controller is returned to its original
status, with or without the new tuning parameters, depending on its initial settings. If the EASY-
TUNE algorithm encounters an abnormal event, the controller is returned to its original settings
and an error status is displayed in datapoint B387.
Section 17. EASY-TUNE
17-7

Table of Contents

Related product manuals