Table D-7. Controller (CON) Modules
Page * Name Atom CON0 CON1 CON2 CON3 Default
Switches
Auto Switch SWA L112 L136 L160 L184 0
Remote Switch SWR L113 L137 L161 L185 0
Auto Enable AE L114 L138 L162 L186 1
Remote Setpoint Enable RE L115 L139 L163 L187 0
Setpoint Track Switch SWSPT L116 L140 L164 L188 0
Output Track Switch SWOVT L117 L141 L165 L189 0
SP Track Enable STE L118 L142 L166 L190 0
Output Track Enable OTE L119 L143 L167 L191 0
SP Track Status SPTS L104 L128 L152 L176 0
Output Track Status OVTS L105 L129 L153 L177 0
Auto Status AUT L107 L131 L155 L179 0
Remote Status RMT L108 L132 L156 L180 0
Alarm A Active PA1 L110 L134 L158 L182 0
Alarm B Active PA2 L111 L135 L159 L183 0
Control Track Command CTC L123 L147 L171 L195 0
Alarm AA Past State LA L126 L150 L174 L198 0
Alarm AB Past State LB L127 L151 L175 L199 0
Process Variable PV C100 C136 C172 C208 0
Control Setpoint TSP C119 C155 C191 C227 0
Deviation DV C121 C157 C193 C229 0
Control Output CO C123 C159 C195 C231 0
Partial Output Term PN C124 C160 C196 C232 0
Reset Feedback RF C127 C163 C199 C235 0
Reset Generator RN H020 H023 H026 H029 0
Rate Generator DN H021 H024 H027 H030 0
Control Tagname TAG A000 A002 A004 A006 CON-0/1/2/3
* For 53MC5000B Firmware only