Parameter Values (Range) Unit Step Default Description
Curve parameter C 0.02...2.00 1 2.00 Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00 1 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for
customer program-
mable curve
Table 234: PHHPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
Table 235: PHIPTOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.2...40.00
1
xIn 0.01 1.00 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Operate delay time
20...200000
2
40...200000
3
ms 10
20
2
40
3
Operate delay time
Table 236: PHIPTOC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases
required for oper-
ate activation
Table 237: PHIPTOC Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
1
In relay patch software 2.1.2, the
Start value
setting range has been extended to start from 0.2
xIn. There is a limitation to the new extended setting range 0.2…1.0 xIn. Firstly, the extended
setting range is settable only from the LHMI. New range values cannot be set from the relay
tools. Secondly, when
Start value
is set below 1.0 xIn, the Operate delay time setting must be ≥40
ms to avoid degrading the relay surge immunity, and to avoid relay faulty operations due to high
surge spikes.
2
REF620 and REM620
3
RET620
1MRS757644 H Protection functions
620 series
Technical Manual
253