Here U represents the measured input voltage. The voltage slope characteristic is
graphically represented.
Figure 167: Effective start value or voltage slope characteristic
To achieve the voltage slope characteristics,
Voltage high limit
must
always be set to a value greater than
Voltage low limit
.
If
Voltage high limit
is lower than
Voltage low limit
, the voltage step
characteristic is active with
Voltage low limit
being the cutoff value.
The value of the setting
Start value
should always be greater than the
setting
Start value low
. Otherwise,
Start value low
is used as the effective
start value.
External input control mode
The External input control mode is used to enable voltage control from an external
application. If
Control mode
is set to the "Input Control" mode, the effective start
value for all phases is influenced by the status of the binary input ENA_U_MULT.
If ENA U MULT isTRUE
Effectivestart value Start value low
_ _ :
=
(Equation 9)
If ENA U MULT is FALSE
Effectivestart value Start value
_ _ :
=
(Equation 10)
Protection functions
1MRS757644 H
330 620 series
Technical Manual