Voltage level Effective start value (I> effective)
U <
Voltage high limit Start value low
U ≥
Voltage high limit Start value
In this example, U represents the measured input voltage. This voltage step
characteristic is graphically represented in
Figure 166
.
Figure 166: Effective start value for voltage step characteristic
The voltage slope characteristic is achieved by assigning different values to
Voltage
high limit
and
Voltage low limit
. The effective start value calculation is based on the
equations.
Voltage level Effective start value (I> effective)
U <
Voltage low limit Start value low
U ≥
Voltage high limit Start value
If
Voltage low limit
≤ U <
Voltage high limit
,
I > (effective)=A -
A-I >
C - D
(C -U)
(Equation 8)
A
set
Start value low
I> set
Start value
C set
Voltage high limit
D set
Voltage low limit
1MRS757644 H Protection functions
620 series
Technical Manual
329