Table 519: HIBPDIF Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operate value 1.0...200.0 %In 1.0 5.0 Operate value, per-
centage of the
nominal current
Minimum operate
time
20...300000 ms 10 20 Minimum operate
time
Table 520: HIBPDIF Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 521: HIBPDIF Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
Table 522: HICPDIF Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operate value 1.0...200.0 %In 1.0 5.0 Operate value, per-
centage of the
nominal current
Minimum operate
time
20...300000 ms 10 20 Minimum operate
time
Table 523: HICPDIF Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 524: HICPDIF Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 10 20 Reset delay time
4.3.5.9 Monitored data
Table 525: HIAPDIF Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
HIAPDIF Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757644 H Protection functions
620 series
Technical Manual
595