Ekip Touch protection release | 10 - Measuring Pro protections
Phase Sequence
Path
Main page - Menus - Advanced protections - Signallings
Function
The Phase Sequence protection trips when the sequence of the voltages is not aligned with
the sequence set by the user.
Parameters
The following is a description of the parameters:
Parameter Description
Enabling Activates/deactivates the protection.
Threshold It defines the voltage control sequence.
Cos φ
Path
Main page - Menus - Advanced protections - Signallings
Function
The protection Cos φ trips when the total cos φ value drops below the threshold set.
NOTE: the total cos φ is calculated considering Total active power and Total apparent
power.
Parameters
The following is a description of the parameters:
Parameter Description
Enabling Activates/deactivates the protection.
Threshold
It defines the value of cos φ below which the protection is
activated
Synchrocheck
Path
Main page - Menu - Advanced protections
Function
The Synchrocheck module recognizes and signals if the synchronism conditions exist
between two independent voltage sources (example: generator + network) for closing of the
interconnection circuit-breaker.
NOTE:
The Synchrocheck functions are activated only in the presence of the Ekip
Synchrocheck module.
All the operating specifications are described in the paragraph that describes the
Synchrocheck module, on page 171.