ABB | SACE Emax 2
22 | © 2013 ABB | 1SDH001000R0002 - L7804
Emax E2.2-E4.2-E6.2 circuit-breakers | 5 - Environmental conditions
5 - Environmental conditions
Installation environment
Install the circuit-breaker in a dry environment, without dust or corrosive acids, and so that is
not subject to shock or vibration.
If this is not possible, mount the circuit-breaker in a framework protecting it adequately.
For the dimensions to be considered for installation, see the chapter "6 - Installation" on page
24 where the following information can be found:
minimum installation volumes of the circuit-breakers and derived versions
distances to be respected for circuit breakers in a cell
overall dimensions of the circuit breakers
drilling of mounting holes
drilling of the cell door
Temperatures of the installation
environment
The mechanical and electrical characteristics are guaranteed between -25 ° C and +70 ° C.
Particular weather conditions
The circuit breaker is designed to operate in particularly difficult industrial environments.
It was tested according to:
IEC 60068-2-1: endurance at low temperatures
IEC 60068-2-2: hot dry climate
IEC 60068-2-30: hot humid climate
IEC 60068-2-52 severity 2: saline mist atmosphere
IEC 60947 (pollution level 3)
IEC60721-3-6 class 6C3
IEC60721-3-2 class 3C2
NOTE: the circuit-breaker is suitable for installation in environments with saline
concentrations no higher than 10 mg/m3.
Dusty environments
It is recommended to install the circuit breaker in suitably ventilated switchgear where
penetration by dust is minimized.
If the environments are dusty (dust> 1mg/m3) it is required to always follow the second level
maintenance procedures.
Vibration
The circuit-breaker is insensitive to mechanical or electromagnetic vibrations that meet the
following standards:
IEC 60068-2-6 a) From 1 to 13Hz with movement equal to 1mm b) From 13 to 100Hz
with constant acceleration equal to 0.7g
Naval specifications: RINA, BV, GL, ABS, LRs, DNV