Ekip Touch protection release | 1 - Layout of the interface
Components of the interface
The operator interface for the Ekip Touch releases appears as follows:
L1
U12
528.9A
95.3V
U12 U31 L1 L2 L3U23 Ne
03:55
A
B
C
D
E
F
G
Figure 65
The following table provides a description of the parts of the interface:
Pos. Description
A Touchscreen display.
B
Power status LED, green. The possible states are:
• Off: power supply absent.
• On, fixed or flashing: power supply present, and release on.
C Warning LED, yellow.
D Alarm LED, red.
E HOME key: opens the main page, or the start page.
F
iTEST key. If the main page or a level 2 page is displayed (see below), pressing it
displays the following pages in succession:
List of Alarms, if there are any messages present.
• With information on the Mainboard and release.
• With information on the circuit-breaker.
Last opening, with information on the last opening.
If the Trip Test item was selected in the Test menu, it runs the opening test.
G Test connector.