ABB | SACE Emax 2
Ekip Touch protection release | 1 - Layout of the interface
59 | © 2013 ABB | 1SDH001000R0002 - L7804
Main page
The main page is the page for accessing the level 2 pages.
The page appears as follows:
Figure 67
The following table provides a description of the various areas of the page:
Pos. Function
A Opens the Histograms page.
B Opens the Menu page.
C Opens the Measuring instruments page.
D Opens the Measurements page.
E In the presence of messages, open the Alarm List page.
Start page
When switched on, the start page is displayed on the display. The system returns automatically
to this page after some minute of inactivity. The default start page is the page Histograms.
Any graphical level 2 page (accessible from the main page) can be set as the start page,
except for the pages Alarm List and Menu.
To set a page as the start page, you need to:
1. Open the page
2. Keep the HOME key pressed for at least 5 seconds.
3. Select Yes in the confirm window that has opened.
Navigation
The following table illustrates how to access the pages through the keys:
To open… Perform these operations…
The main page Press the HOME key.
The start page Press the HOME key, until the start page appears.
The Alarm List page
If there are messages present, if the diagnostics bar is
displayed:
• Touch the display in the message display area, or
• Press the iTEST button.